Brand: Bently Nevada
P/ n:3500/25
Description: Enhanced Keyphasor module
Origin: United States
Xiamen Xiongba provides 3500/25 DCS/PLC, Xiamen Xiongba Shan Ni for your quotation, and provide a year warranty service.
3500/25 quality high price affordable available in a variety of models.
Xiamen Xiongba Electronic Commerce Co., LTD. (Zhangzhou Branch)
Unit 2009, Creative Center, 1733 Luling Road, Siming District, Xiamen, China
M: + 86 18059884797
Email :sales@xiongbagk.cn
Website:www.sauldcs.com/www.xiongbagk.cn
The 3500/25 improved key phaser module is a half height, 2 channel module used for monitors in the 3500 frame
Module provides key phase signal. This module receives input signals from eddy current sensors or electromagnetic sensors and converts them
The signal is a digital key phase signal that indicates when the key phase mark on the rotating shaft passes through the key phase probe. each
The key phase module has 2 input channels. The 3500 mechanical protection system can install 2 key phase module to receive 4 key phase signals.
Note: The key phase signal is a pulse signal from the rotating shaft or gear once per revolution or more than once per revolution, providing accurate
Time measurement. The 3500 monitor module and external fault diagnosis equipment are allowed to measure vector parameters such as 1X amplitude and phase
The number.
Each key phase module can receive 2 signals from eddy current sensors or electromagnetic sensors. The input signal range is
-0.8V to -21.0V(non-insulated I/O module) and +5V to -11V(insulated I/O module). The module can be limited amplitude, so that the signal is not
Exceed this range. The passive electromagnetic sensor requires a shaft speed greater than 200rpm(3.3Hz). On the front panel of the frame, through coaxial
Connector, with 2 buffer keys phase output signal. Two buffer key phase outputs are also available on the back of the frame, via European connectors
Get it. Front panel LED OK indicator: indicates that a fault has been detected in the key phase module. TX/RX refers to
Indicator: indicates when the key phase module communicates with the frame interface module (RIM).
1) Buffer sensor output