PM 783F 3BDH000364R0005
- Central Processing Unit (2 MB)
- Without operating system. The operating system has to be loaded during software installation.
- Needs external 24 VDC power supply
- Software version 2013 SP1 RU04, 2016 SP1 RU03 or higher is mandatory.
- For details, refer to the Freelance AC 700F Compatibility Matrix (2PAA106303D0002 C).
- Terminal Base TB 711F and Battery TA521 are not included
The Central Processing Unit (CPU) module is equipped with a high-performance processor for fast loop cycle times. It comes with on-board 100 Mbit/s Ethernet network connection used for communication between controllers, operator stations, and engineering tool. Two serial line interfaces complement the connectivity. One interface can be used for Modbus communication, while the other is used for diagnostics. For demanding applications, eight cyclic and priority driven tasks with adjustable cycle time can be configured, as well as a cyclic PLC type task, which runs as fast as possible. This multi-tasking scenario enables engineers to design applications that reflect all demands of process control, while at the same time balancing the CPU load. This keeps the resources needed in a project at the minimum.
The small front panel display shows status and diagnostic information directly at the module. Furthermore, you can lock the controller via the keys. This means, the controller can be blocked for downloads of application and firmware to enhance security. The status, if the controller is locked or unlocked is shown on the display.
Technical data PM 783F
CPU Freescale PowerPCTM
RAM Program memory (battery backed up) 2 MB SRAM
Internal memory 8 MB SDRAM, 4 MB FLASH ROM
Processing time for 1000 instructions 0.71 ms for binary instructions
0.84 ms for word instructions
1.36 ms for floating point instructions
Max. number of I/O modules on I/O bus (direct I/O) 8
Power supply 24 V DC
Max. power dissipation within the module 10 W
Current consumption from 24 VDC 80 mA (max)
Inrush current at 24 VDC 1 A²s
Data backup source Lithium battery
Data buffering time at 25 °C / 77 °F Approximately 1.5 years
Battery low indication Warning indication issued about 2 w