ABB Controller AC800F Overview ABB Controller AC800F uses standard Ethernet as the system communication bus, the bus standard is DIN ISO 8802.3. Ethernet module is the interface device between controller and system bus. ABB Controller AC800F Design 2 slots for inserting various types of Ethernet modules, with F1… Ethernet modules cannot be inserted or removed when the ABB controller AC800F is running. The different types of Ethernet modules mainly meet the needs of different communication media. All Ethernet modules have a battery circuit, when the ABB controller AC800F power off, by the battery to maintain the controller main memory information and system real-time clock data. When only one Ethernet module is used, the dedicated battery module M801F/AM811F can also be inserted into the El/E2 slot to provide high energy retention. Use EI811F EI812F EI813F, AM811F module with PM803FCPU plate, used to provide energy electricity kept 16 MB memory information if the battery voltage is lower than the prescribed limit, the module send out alarm signal, the CPU will identify the signal and generate alarm message system. Unlike F1… F4 slot, Ethernet module is specially used for E1 and E2 slot, through special DMA fast data communication technology, realize the CPU and main memory and system bus device data processing. Module heddle features a status LED display
A battery voltage monitoring status LED display
Automatic module recognition. After the module is powered on and started, the CPU reads special boot parameters from the EEPROM of the module. Once normal, the module is connected to the internal system bus of ABB controller AC800F, and the controller begins to process and calculate with this module
Access to the ABB controller AC800F and Ethernet modules is via an internal data bus, allowing maximum data flow through, with data bandwidth up to 100Mbps
Ethernet modules have their own dedicated communication processing chip, and its corresponding curing program, which also supports upgrading through the system bus
Each module can generate its own interrupts that are identified and processed by the system according to different priorities
Fault data stored in the module memory can be reported to ABB controller AC800F by a specialized fault level interrupt processing
Reserve 8MB memory for accessing the address domain and 8MB /O memory for accessing the address domain
The module supports connection to 8-bit, 16-bit, and 32-bit data buses. The memory domain and I/O domain of the module can be configured to different data buses
Battery low voltage monitoring and alarm