The 1900/65 Universal Equipment Monitor is a mechanical vibration monitor,
Designed for continuous monitoring and protection for a variety of applications
And industry equipment. The low cost of 1900/65 made it a machine and
Ideal solutions for processes, these machines and processes can benefit from continuous monitoring and protection, but cannot prove it
The cost of traditional displays.
input
The 1900/65 provides four vibration inputs and four temperature inputs. Each vibration
The input can be configured by software to support 2-wire and 3-wire accelerometers and speed sensors
Or proximity sensor. Temperature input supports E, J, K and T thermocouples.
output
Six relay outputs are available, available
Logical statement pairs defined by users
The normal, alert, and hazardous states of any channel or combination of channels are operated by programming them to open or close contacts.
Four 4-20 mA logger outputs are provided. Each logger output is available through software
Configure to output any variable from any channel.
The input signal for each vibration input can also be used for a dedicated buffered output.
Modbus gateway provided as an option, allowing the monitor will be static
Variable, status, event list, the time and date information provided directly to any of the Modbus client,
Including distributed control systems (DCS), monitoring and data acquisition
(SCADA) system, programmable logic controller (PLC), or 1 system. monitor
Generated using an internal counter and a time reference sent from the Modbus® client
Time and date. When ordering not equipped with Modbus monitor can through the gateway
Order the 1900/01 Communications upgrade to upgrade (see Ordering Information section).
Modbus/TCP (Ethernet) to Modbus/RTU (serial) converters are available to support serial
Modbus (see attachment).
configuration
Monitor operations and Modbus register mapping by gateway
Use software running on your laptop or PC to create a configuration file and
Defined by downloading files to the monitor via a built-in Ethernet connection. Configure the permanent storage of information
In non-volatile memory, changes can be uploaded to a PC.
Display module
The 1900/65 monitor can be operated with an optional monitor/keyboard when applied
When you need to be able to view channel information or make minor configuration changes
A separate package. If desired, the display can be installed in
The maximum distance from the monitoring module is 75 meters (250 feet).
Characteristic summary
• Continuous monitoring and protection applies
Automatic shutdown application
• The monitor can be used for standalone operation or via 10BaseT/100BaseTX
Ethernet uses Modbus/TCP for communication networking • Small package. Monitoring module: 196.9 mm x 149.4 mm x 74.4 mm (7.75 “x 5.88” x 2.93 “). Monitor module with display module: 196.9 mm x 149.4 mm x 97.8 mm (7.75 “x 5.88” x 3.85) “• Can be mounted on DIN rails or dividers • Accepts 18 to 36 Vdc power supply. Optional 110-220 Vac external power supply • 24-bit ADC conversion • Four vibration/position inputs • four temperature inputs
• Configurable scale factors and full scale ranges
• Up to four processing variables per channel, with
Independent integration and filter control
• Internal OK check status
• Independent alert and hazard setting points
• Event list
• Six relay outputs. Relay operation is programmable
• Buffered output for each sensor channel
• Four configurable 4-20 mA recorder outputs
• Optional NEMA 4X/IP68 fiberglass case with
Window for display • For panel mounting display
Painted or stainless steel weatherproof doors • Certified for hazardous areas