Bentley Bentley 3500 configuration requirements
Each key compressor unit is equipped with a Bentley 3500 frame
Each Bentley 3500 frame is equipped with redundant 3500/15 power modules
Each Bentley 3500 frame is equipped with 3500/22m transient data interface module;
For the above key phase measurement points, the corresponding 3500/25 key phase module is configured in the Bentley 3500 frame of each unit
The corresponding 3500/42M monitor module must be configured for the above measuring points of axial vibration, axial displacement, tile vibration and shell vibration
(if applicable), corresponding 3500/60, 61 temperature monitoring modules or 3500/62 process quantity monitoring modules shall be configured for the above bearing temperature measuring points
Each monitoring channel (shaft vibration, shaft displacement and tile vibration) is configured with two independent relay output channels; Use 3500/32 (4 channels) or 3500/33 (16 channels) relay module