MTL831B  IS Analogue Multiplexer Transmitter

1 ABOUT THIS MANUAL
The purpose of this manual is to provide the user with information on the installation, connection and configuration of the MTL831B analogue mutliplexer transmitter.

1.1 Related documents
This manual does NOT cover the connection or configuration of the MTL838B-MBF receiver. For details of this item consult:
♦ INM838B-MBF.
Additional application information is available in:
♦ AN9010.

Category:

Description

MTL831B  IS Analogue Multiplexer Transmitter

Product description

1 ABOUT THIS MANUAL
The purpose of this manual is to provide the user with information on the installation, connection and configuration of the MTL831B analogue mutliplexer transmitter.

1.1 Related documents
This manual does NOT cover the connection or configuration of the MTL838B-MBF receiver. For details of this item consult:
♦ INM838B-MBF.
Additional application information is available in:
♦ AN9010.
1.2 Product description
The MTL831B analogue transmitter can transfer a number of hazardous area input signals to the safe area down a data highway consisting of a single twisted pair cable. It is intrinsically safe and can therefore be mounted in Zone 0 hazardous areas or Class I, Division 1 hazardous locations.
The MTL831B can monitor up to 16 inputs from THC or millivolt sources or up to 15 inputs from 2, 3 or 4-wire RTDs.
Two (i.e. dual redundant) data highway outputs are provided that can carry both signal and power over distances up to 3km, depending on the application, the cable and the (noise) environment – see Section
4.4. The highway cables can be simple twisted-wire pairs or pairs of wire within an IS multi-core cable.

At the other end of the data highway, MTL838B-MBF receivers are used to translate the information transmitted from the MTL831B. The MTL838B-MBF provides a Modbus® serial data output representation of the inputs together with status information.
When the MTL831B transmitter is mounted in the hazardous area, each data highway must be protected by an MTL3052 digital isolator mounted in the safe area.

MTL831B

Product parameter

The main parameters of the MTL831B product include:

Power supply voltage: DC 12-32V.
Temperature measurement range: -200℃ to +850℃.
Temperature sensor type: Thermocouple, RTD.
Output signal type: 4-20mA, HART.
Accuracy: ±0.1% FS.
Operating temperature range: -40℃ to +70℃
Product size: 52mm x 20mm x 114mm.
Product weight: about 100g
Shell material: aluminum alloy.
Import protection grade: IP20
Mounting method: 35mm DIN rail mounting.
Number of channels: Depending on the model, there are options for 16-channel thermocouples and 15-channel RTDS.
Explosion-proof class: Exia IICT4.
Installation Zone: Zone 0 IIC T4
Power supply: loop power supply, 12VDC
In addition, MTL831B products are widely used in petroleum, chemical, electric power, metallurgy and other industrial fields, mainly for measuring and controlling temperature changes. It can be used with a variety of thermocouples and RTD sensors, with high accuracy and stability, making it ideal for industrial automation control systems.

Application field

2 GETTING STARTED
Installation of the MTL831B multiplexer transmitter is divided into three main topics.
♦ Mechanical Installation – how to mount the MTL831B and how it may be fitted into our enclosure.
♦ Electrical Connections – the sensor and highway connections. If units are installed in our enclosures, it details any special wiring arrangements.
♦ Configuration – the address and input mode selection by the setting of internal switches.
3.1 Location
The MTL831B can be installed in either safe or hazardous areas (including Zone 0 or Division 1) depending upon the requirements of the application.
3.2 Mounting options
The unit can be mounted on T-section DIN-rail or onto a flat surface. Eaton has a range of enclosures – ENC8, ENC8-SS, ENC83 or ENC83-SS – to provide suitable IP67 protection if the transmitter is located in an exposed area.
3.2.1 Mounting on T-section DIN-rail (Figure 1)
Hook the side opposite the central mounting clip onto standard 35mm DIN46277 T-section rail and push downwards until the unit clicks into place.
To remove, ease the central clip below the base of the unit outwards (with a screwdriver) and unhook the clips on the other side.