UG10 8526-653 UG-10 Dial or Lever Governors

Mounting base dimensions for the UG-5.7, UG-8, or UG-10 Dial or Lever Governors are identical. See Figure 1 for mounting base dimensions. Place a gasket between the base of the governor and the engine mounting pad. Mount the governor squarely on its mounting pad and in line with the drive. Torque the mounting bolts evenly. There must be no movement or rocking of the actuator on the engine mounting pad.

Use the correct coupling between the governor and the prime mover drive. Be sure there is no binding, excessive side loading of the governor drive shaft, or looseness in the coupling. There must be no force pushing the governor drive shaft into the governor.

A misaligned drive shaft could break and could cause an overspeed condition or runaway engine.

If the engine drive pad is at an angle (from 0 degrees to 45 degrees maximum), the governor must be installed with the front panel in the upper position.

If an optional keyed drive is used when installing the governor, avoid rough gear teeth and incorrect backlash. Refer to the prime-mover manufacturer’s specifications for the correct amount of backlash and adjustment procedure.

Category:

Description

UG10 8526-653 UG-10 Dial or Lever Governors

Product Description

Mounting base dimensions for the UG-5.7, UG-8, or UG-10 Dial or Lever Governors are identical. See Figure 1 for mounting base dimensions. Place a gasket between the base of the governor and the engine mounting pad. Mount the governor squarely on its mounting pad and in line with the drive. Torque the mounting bolts evenly. There must be no movement or rocking of the actuator on the engine mounting pad.

Use the correct coupling between the governor and the prime mover drive. Be sure there is no binding, excessive side loading of the governor drive shaft, or looseness in the coupling. There must be no force pushing the governor drive shaft into the governor.

A misaligned drive shaft could break and could cause an overspeed condition or runaway engine.

If the engine drive pad is at an angle (from 0 degrees to 45 degrees maximum), the governor must be installed with the front panel in the upper position.

If an optional keyed drive is used when installing the governor, avoid rough gear teeth and incorrect backlash. Refer to the prime-mover manufacturer’s specifications for the correct amount of backlash and adjustment procedure.

UG-8L

Product parameter

The recommended continuous operating temperature of the oil is 60 to 93 °C (140 to 200 °F). The ambient temperature limits are –29 to +93 °C (–20 to +200 °F.

Use Tables 1 and 2 as a guide in the selection of a suitable lubricating hydraulic oil.

Measure the temperature of the governor on the outside lower part of the case.

The actual oil temperature will be slightly warmer by approximately 6 Celsius degrees (10 Fahrenheit degrees).

Fill the governor with the selected oil to the mark on the oil sight glass. Oil must be visible in the glass under all operating conditions.

Application field

Start the engine as instructed by the engine manufacturer. For a safe start-up, adjust the speed setting knob on the governor for a reduced speed and allow the engine to warm up.

Once the governor has reached its operating temperature, make the following compensation adjustments without load on the prime mover:

  1. Bleed trapped air from the governor oil passages using the following procedure:

Loosen the nut holding the compensation adjusting pointer and set the pointer as far as it will go towards maximum compensation. Tighten the nut.

Open the needle valve two turns ccw.

Allow the prime mover to hunt for approximately 30 seconds to bleed trapped air.

  1. Loosen the nut holding the compensation pointer and set the pointer as far as it will go towards minimum compensation. Tighten the nut again.
  1. Gradually close the needle valve until hunting stops. If hunting does not stop, open the needle valve three to five turns from the closed position, and move the compensation pointer up by two marks on the front panel indicator scale. Again, gradually close the needle valve until hunting stops. If hunting does not stop, repeat this procedure.
  1. Check governor stability by manually disturbing the governor speed setting.

The compensation adjustment is satisfactory when the governor returns to speed with only a slight overshoot or undershoot.

  1. The needle valve must not be closed completely, normal position is from 1/2 to 3/4 turn open. Closing the needle valve more than necessary makes the governor slow to return to normal speed after a load change. It is also desirable to have as little compensation as possible. Once the needle valve adjustment is correct, it is not necessary to change the setting except for large changes in temperature which affect governor oil viscosity.
  1. When the compensation adjustment is correct, tighten the compensation pointer, and install the needle valve access plug and seal washer.

Other related product recommendations:

MVI56-ADM  Prosoft  Programmable Application Development Module
BMXCPS2010  Schneider  Standard power module
BMXDDO6402K  Schneider  discrete DC output module
BMXDDI3202K  Schneider  discrete input module
PCI-6221  779066-01  Multifunction I/O Device
SHC68-68-EPM  NI  Multifunctional cable
05701-A-0361  Backplane Serial communication controllers and monitors
AI03  ABB   AI module  2-3-4 Wire RTDs
AI02J  ABB   AI module  2-3-4 Wire RTDs
IOC-555-D 17-550555-001  GE  Electronic components
PC834-001-T  PACIFIC SCIENTIFIC Brushless Servo Drive
8440-1666 B  SPM-D11/LSXR features 12/24 VDC power supply
IC670ALG310  GE  voltage-source analog output module
PM866K01 3BSE050198R1  AC800M processor unit
81001-340-71-R  Allen Bradley  Inverter processing module
PXI-8423  NI  PXI-8423/2 RS-485 Interface
AD02  ABB   AI module  2-3-4 Wire RTDs
MVME55006E-0163  MOTOROLA  VMEbus Single-Board Computer
531X301DCCAFG2  GE  DRIVE CONTROL BOARD
A6370D  Emerson  A6370 Overspeed Protection Monitor
1715-TASOB8DE  Allen Bradley  termination assembly
4PP065.0571-X74F  Power Panel PP65
2094-BC02-M02   Kinetix 6000 Integrated Axis Module (IAM)
MVI56E-MCM  ControlLogix series communication module
1769-L32E  CompactLogix Modular controller
DI810  16  Digital Input  module

Please contact Sunny sales@xiongbagk.cn for the best price.

➱ sales manager: Sunny
➱ email mailto: sales@xiongbagk.cn
➱ Skype/WeChat: 18059884797
➱ phone/Whatsapp: + 86 18059884797
➱ QQ: 3095989363
➱ Website:www.sauldcs.com